Flowair
Flowair LEO air heater 1.7 to 65.2 kW with swivel bracket
Flowair LEO air heater 1.7 to 65.2 kW with swivel bracket
Flowair LEO water-to-air heater for halls, workshops and warehouses, supplied with heating water. 4 sizes according to page: LEO S2 2.1 to 26.5 kW, LEO S3 1.7 to 32.7 kW, LEO L2 2.2 to 50.4 kW, LEO L3 3.2 to 65.2 kW. Three fan speeds, 230 V, 50 Hz. Swivel bracket included, TS 14565 controller optional. Sizing according to heating load and water temperature available on request.
incl. VAT + Shipping Costs
Crowd
Couldn't load pickup availability
- Brand-name units from a specialist retailerOriginal products from leading manufacturers
- Personal adviceBy phone, email or WhatsApp
- Installation on requestBy specialist installers in your region
- Secure paymentPayPal with Buyer Protection, credit card and more
Description
Description
With the Flowair LEO, you heat halls using the existing heating water: the heat exchanger extracts heat from the heating circuit, and the fan blows the warm air into the room. On this page, you can choose between 4 sizes (LEO S2 (51949), LEO S3 (51950), LEO L2 (51955), LEO L3 (51956)) with heating capacities according to the page of 1.7 to 65.2 kW* and optional accessories, including a 3-stage TS 14565 control unit. The unit is connected to 230 V, 50 Hz; three fan speeds.
Performance and range of application
Heating capacity according to the page: LEO S2 (51949) 2.1 to 26.5 kW (rated capacity 10.2 kW at 70 / 50 / 16 °C); LEO S3 (51950) 1.7 to 32.7 kW (rated capacity 12.3 kW at 70 / 50 / 16 °C); LEO L2 (51955) 2.2 to 50.4 kW (rated capacity 19.1 kW at 70 / 50 / 16 °C); LEO L3 (51956) 3.2 to 65.2 kW (rated capacity 25.6 kW at 70 / 50 / 16 °C). The performance ranges according to the page vary by model; the page states the rated capacity at 70 / 50 / 16 °C (flow / return / air inlet) on stage III. The range for each model is determined by the heating water: at boiler temperatures, the unit achieves the upper end of the performance range, while with low-temperature water from a heat pump, it achieves less. We can determine whether one size is sufficient or several units are required upon request based on the heating load. Range of application: according to the page, indoor spaces with a maximum dust load of 0.3 g/m³: industrial, warehouse, commercial, sports, and religious buildings, as well as workshops, garages, shops, car dealerships, and gas stations; maximum operating ambient temperature 60 °C.
* The heating capacity of an air-to-air heater depends on the flow and return temperatures of the heating water, the air inlet temperature, and the fan speed; the range stated on the page covers these operating points. The number and size of the units are determined by the calculated heating load of the hall, not the floor area. The design must be tailored to the specific property. To determine the design for your property, please contact us.
Key benefits at a glance
- 4 sizes from 1.7 to 65.2 kW according to the page (LEO S2 (51949), LEO S3 (51950), LEO L2 (51955), LEO L3 (51956)), with one page for the entire range.
- Airflow up to 3800 m³/h according to the table (stage III, model LEO L2 (51955)), horizontal throw up to 21.5 m,
- Three fan speeds, protection rating IP 54, insulation class F; power consumption according to the table from 130 W.
- Optional accessories: TS 14565 control unit, rotary console.
- Housing: EPP, grey (according to the page, similar to RAL 9007).
- Heating water up to 120 °C, operating pressure up to 1.6 MPa according to the page.
Detailed functions
Heat exchanger and heating water
Heat exchanger: the page does not provide specifications for the heat exchanger; rated capacity at 70 / 50 / 16 °C according to the table. Connection 1/2 inch (S) or 3/4 inch (L). Maximum heating medium temperature 120 °C, maximum operating pressure 1.6 MPa according to the page. We can check the performance at low flow temperature, for example with a heat pump, for your operating point upon request.
Fan and air distribution
Three fan speeds, protection rating IP 54, insulation class F. Airflow, sound pressure level, and throw for each speed are shown in the table below. The page does not provide specifications for the air-directing louvres.
Control and accessories
TS 14565 control unit as an option: manual selection of the three fan speeds, heating and ventilation operating modes according to the page; the page does not state that the TS includes a thermostat.
Installation
Rotary console included in every set according to the page; the page does not provide installation instructions. Installation, hydraulic connection, venting, and electrical connection must be carried out by a specialist company.
Scope of delivery
Depending on the selected option according to the page:
- LEO S2, S3, L2, or L3, each with a rotary console: air heater and rotary console
- optional with TS 14565 3-stage control unit: air heater, rotary console, TS control unit
Additional items required
- Heating water supply with flow and return (boiler, heat pump, or district heating), piping to the unit, shut-off valves, and, if required, a valve with an actuator
- 230 V, 50 Hz electrical supply with circuit breaker, control cable to the controller
- Installation, hydraulic and electrical connection, and commissioning by a specialist company
Technical data
| Model | LEO S2 (51949) | LEO S3 (51950) | LEO L2 (51955) | LEO L3 (51956) |
| Heating capacity according to the page | 2.1 to 26.5 kW | 1.7 to 32.7 kW | 2.2 to 50.4 kW | 3.2 to 65.2 kW |
| Rated capacity at 70 / 50 / 16 °C, stage III | 10.2 kW | 12.3 kW | 19.1 kW | 25.6 kW |
| Max. airflow | 2000 m³/h | 1800 m³/h | 3800 m³/h | 3400 m³/h |
| Max. sound pressure level | 56.3 dB(A) | 56.3 dB(A) | 64.1 dB(A) | 64.1 dB(A) |
| Max. sound power level | 71.4 dB(A) | 71.4 dB(A) | 79.2 dB(A) | 79.2 dB(A) |
| Max. power consumption | 130 W | 130 W | 340 W | 340 W |
| Max. current draw | 0.6 A | 0.6 A | 1.5 A | 1.5 A |
| Horizontal / vertical throw | 14 m / 5.3 m | 12.5 m / 4.9 m | 21.5 m / 7.5 m | 19 m / 6.8 m |
| Heating water connection | 1/2 inch | 1/2 inch | 3/4 inch | 3/4 inch |
| Max. heating medium temperature / operating pressure | 120 °C / 1.6 MPa | 120 °C / 1.6 MPa | 120 °C / 1.6 MPa | 120 °C / 1.6 MPa |
| Power supply | 230 V, 50 Hz | 230 V, 50 Hz | 230 V, 50 Hz | 230 V, 50 Hz |
| Weight (empty / with water) | 10.4 kg / 11.6 kg | 10.8 kg / 12.2 kg | 16.2 kg / 18.2 kg | 17.8 kg / 20.5 kg |
| Dimensions | only as a drawing on the page (LEO S and LEO L) | only as a drawing on the page (LEO S and LEO L) | only as a drawing on the page (LEO S and LEO L) | only as a drawing on the page (LEO S and LEO L) |
| Housing | EPP, grey (according to the page, similar to RAL 9007) | EPP, grey (according to the page, similar to RAL 9007) | EPP, grey (according to the page, similar to RAL 9007) | EPP, grey (according to the page, similar to RAL 9007) |
| Manufacturer according to the page | not stated on the page | not stated on the page | not stated on the page | not stated on the page |
Frequently asked questions
Which size of the Flowair LEO is suitable for my hall?
The basis is the heating load calculation of the hall together with the available flow temperature; the performance range according to the page extends from 2.1 to 26.5 kW to 3.2 to 65.2 kW. Depending on the size of the hall, one or more units may be suitable. We can determine the design upon request.
What water temperature does the air heater require?
The page states 120 °C as the maximum heating medium temperature and 1.6 MPa as the maximum operating pressure. The unit also operates at a lower flow temperature, but delivers less performance; for heat pump operation, we can check the operating point upon request.
What is included in each option?
According to the page: LEO S2, S3, L2, or L3, each with a rotary console: air heater and rotary console; optional with TS 14565 3-stage control unit: air heater, rotary console, TS control unit. Piping, shut-off valves, electrical supply cable, and installation materials are not included.
How is the air heater controlled?
TS 14565 control unit as an option: manual selection of the three fan speeds, heating and ventilation operating modes according to the page; the page does not state that the TS includes a thermostat. We can clarify which control system is suitable for your system, for example with several units or a building management system, upon request.
How loud is the unit and how far does the airflow reach?
According to the table: LEO S2 (51949) 56.3 dB(A), throw 14 m horizontally and 5.3 m vertically; LEO S3 (51950) 56.3 dB(A), throw 12.5 m horizontally and 4.9 m vertically; LEO L2 (51955) 64.1 dB(A), throw 21.5 m horizontally and 7.5 m vertically; LEO L3 (51956) 64.1 dB(A), throw 19 m horizontally and 6.8 m vertically. At the lowest speed, the sound pressure level decreases, and the throw also decreases.
Can I connect the air heater to a heat pump?
In principle, yes. The heat exchanger extracts heat from the heating water, regardless of whether it comes from a boiler or a heat pump; at heat pump temperatures, only a portion of the range is usable. We can determine the appropriate design upon request.
Where is the unit installed?
Rotary console included in every set according to the page; the page does not provide installation instructions. The airflow should point toward the occupied area without blowing directly on people; the throw according to the table helps in choosing the installation location.
Can I install and connect the air heater myself?
No. Installation, hydraulic connection with venting, electrical connection, and commissioning must be carried out by a specialist company; this also applies to the connection of the controller and a valve with an actuator.
Important Note
Important Note
Dear Customer, please note that by purchasing this product, the buyer/user confirms compliance with Regulation (EU) No 517/2014 of the European Parliament and of the Council of 16 April 2014 on fluorinated greenhouse gases and Regulation (EU) No 573/2024 of the European Parliament and of the Council of March 2024 on fluorinated greenhouse gases, which stipulates the following: The person who buys/uses the split air conditioner confirms that it will be professionally installed by certified professionals.
F-Gas Regulation Download Declaration

Contact Us
Hinweis zu Kundenbewertungen: Bewertungen mit dem Kennzeichen „Verifiziert“ stammen von Kunden, die das Produkt bei uns gekauft haben. Die Prüfung erfolgt automatisch durch unseren Bewertungsdienst Judge.me anhand der Bestelldaten. Bewertungen ohne dieses Kennzeichen wurden über das Formular auf dieser Seite abgegeben. Bei diesen Bewertungen wird nicht geprüft, ob das Produkt tatsächlich gekauft wurde.